12.6 H: Terminal Function Selection
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting
0
2
ON : Output frequency < value of E1-09 or b2-01.
OFF : Output frequency ≥ value of E1-09 or b2-01.
2: Speed Agree 1
Setting Value
Function
2
Speed Agree 1
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of "frequency reference ± L4-02".
OFF : The output frequency does not align with the frequency reference although the drive is
running.
3: User-Set Speed Agree 1
Setting Value
Function
3
User-Set Speed Agree 1
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection
level.
ON : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency
reference ± L4-02.
OFF : The output frequency is not in the range of "L4-01 ± L4-02" nor the range of frequency
reference ± L4-02.
312
Control Method Selection
V/f
OLV
Figure 12.11 Zero Speed Time Chart
V/f
OLV
The terminal activates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection
Width].
Figure 12.12 Speed Agree 1 Time Chart
V/f
OLV
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree
Detection Width] and in the range of the frequency reference ± L4-02.
Parameter Used as the Reference
E1-09
b2-01
Description
Description