Type &
Object name
Instance
Minimum cooling
temperature
setpoint
AV 39
Maximum Heating
temperature
AV 40
setpoint
Minimum Fan
Output
AV 41
Maximum Fan
Output
AV 42
Low Fan Speed
AV 43
Setting
Med. Fan Speed
Setting
AV 44
Hi Fan Speed
AV 45
Setting
Minimum Off
AV 46
Time
Minimum On Time
AV 47
Stroke Time
AV 48
Set Point for
Humidity
AV 49
Dew Point Set
AV 50
Point
Occupancy Status
BI 0
Window-Door Status BI 1
Cooling-heating
BI 2
Status
Relay 1 Status
BI 3
Relay 2 Status
BI 4
Relay 3 Status
BI 5
Relay 4 Status
BI 6
Relay 5 Status
BI 7
Relay 6 Status
BI 8
UM-15095000-AA0
Readable/
Description
Writable
Minimum cooling
R/W
temperature setpoint
Maximum Heating
R/W
temperature setpoint
Minimum Fan Output at
Auto Fan Mode (for
Modulating Fan Application) 0%~Reg 51
R/W
Maximum Fan Output at
Auto Fan Mode (for
Modulating Fan
R/W
Application)
Low Fan Speed Setting (for
R/W
Modulating Fan
Application)
Med. Fan Speed Setting
(for Modulating Fan
Application)
R/W
Hi Fan Speed Setting(For
R/W
Modulating Fan
Application)
R/W
Minimum Off Time
R/W
Minimum On Time
Stroke time
R/W
Set Point for
Humidity Control
R/W
Dew Point
R/W
Temperature Set Point
R
Status of Occupancy
R
Window/ Door Status
Status of
Cooling/Heating Control
R
Output
Status of Relay 1
R
(Output Stage 1)
Status of Relay 2
R
(Output Stage 2)
Status of Relay 3
R
Status of Relay 4
R
Status of Relay 5
R
Status of Relay 6
R
Range and Definition
°C 0-500 (0.0 ~50.0 C)
F320-1220 (32-122.0 F)
°C 0-500 (0.0 ~50.0 C)
F320-1220 (32-122.0 F)
Reg 50~100%
0%~Reg 53
Reg 52~Reg54
Reg 53~100%
0~180 seconds
0~180 seconds
10~1600 sec.
0~1000 (0.0~100.0
%RH)
-999~9999: -99.9~999.9
℃/°F
0: Room Occupied
1: Room Unoccupied
0: Door/Window Closed
1: Door/Window Open
0: Close & Off 1: Open & On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On