Installation Of The Outdoor Unit; Installation Precautions - Fujitsu Waterstage GENERAL WOHG112LHT Manual

Air to water heat pump
Table of Contents

Advertisement

Air to Water Heat Pump split system
2 .4

Installation of the outdoor unit

2 .4 .1 Installation precautions

" The outdoor unit must only be installed outdoor
(outdoors). If a shelter is required, it must have
broad openings on the 4 walls and observe the
installation clearances
• Choose the location of the appliance after discussion
with the client.
• Choose a site that is preferably sunny and sheltered
from strong cold predominant winds.
• The unit must be easily accessible for future installation
and maintenance work
• Ensure that it is possible to make the connections to
the hydraulic unit easily.
A ≥ 150 mm
B ≥ 200 mm
C ≥ 250 mm
D ≥ 300 mm
E ≥ 500 mm
G
C
C
F
G
figure 13 - Minimum installation clearances around outdoor unit (all models)
- 14 -
(figure
13).
(page
16).
F ≥ 600 mm
G ≥ 1000 mm
H ≥ 1500 mm
J ≥ 2000 mm
K ≥ 3000 mm
G
C
D
C
A
C
J
H
• The outdoor unit is able to withstand bad weather but
avoid installing in a position where it is likely to be
exposed to significant dirt or flowing water (under a
defective gutter for example).
• Water may drain away from the outdoor unit when it
is operating. Do not install the appliance on a paved
terrace; choose a well-drained place (e.g. gravel
or sand). If the installation is in an area where the
temperature can be lower than 0°C for a long period,
check that the presence of ice does not present any
danger. A drainage pipe can also be connected to the
outdoor unit
(see figure 14, page
• Nothing should obstruct the air circulation through the
evaporator and from the fan
• Keep the outdoor unit away from heat sources and
inflammable products.
A
C
H
H
C
C
E
D
15).
(figure
13).
B
A
B
G
D
C
E
C
C
C
C
C
F
H
Installation and operating manual "1775 - EN"
D
H
E
E
E
H
F
K