System Components Control and Safety Devices • System Controller (SFC-50) Incorporated PLC-based Timer Memory retention during power outages Alarm Indicator Light(s) Control Circuit Breakers (CB1, CB2) Pump Control Selector Switch {Hand (Manual) / Off / Auto} System Power Indicator Light Pump Running Indicator Light(s) Alarm Reset Push Button PLC Navigational Control Buttons...
Pump will not be allowed to run until the alarm is addressed and reset. Note: If the Pump Overload Alarm triggers, please contact AXI International. Once triggered alarms are addressed, each alarm can be reset via the System Controller. – See provided controller manual for instructions on alarm resets.
If Applicable Manual Additive Injection – Note: Manual Additive Injection operation may vary depending on the vertical and horizontal distance between the Additive Holding Container and Fuel Polishing System. 1. With the system running, place flexible hose between the Additive Injection Port and Additive Container. 2.
Primary Inspection Upon arrival, the system and accessories must be visually inspected before installation. Improper handling during shipping may cause physical or electrical problems. Immediately report or note any damages to the shipper. Checklist If the packing crate shows signs of damage inspect the system for damage. Check the entire system for damage that could indicate internal mechanical or electrical problems.
If the motor is running in the wrong direction, contact AXI International immediately. !WARNING!: The whole system (enclosure, plumbing, motor, electric sub panel) must be properly grounded for operator safety.
Remote Shutdown – Interlocks: The customer can provide interlocks connected to the System Controller in order to establish external shutdown capabilities of the system’s Pump. Note: The 24 V DC provided by the power supply in the electrical box of the system must be used for remote shutdown Plumbing Note: Please ensure to check all of the plumbing (joints, unions, miscellaneous fittings) for tightness prior to completion.
Also, it is highly recommended to plumb the discharge line independent separate from the engine’s fuel return. If the return line from the engine and the discharge of the system must be combined in any way, adequate valves should be installed to prevent any possible interference with safe engine operation.
System Controller Setting the Current Date and Time 1. Please make sure the selector switch is set to “OFF” and push the Alarm Reset button on the enclosure door panel. 2. When power is first applied to the system, the display of the PLC will show (blinking) the date and time. 3.
Priming the System The Pump supplied with the system is NOT automatically self-priming and must not be run dry. !WARNING! If the Pump is allowed to run without fuel, Pump damage can occur. Priming Procedure The head of the Pump on the system is shipped from the factory filled with No. 2 Diesel Fuel Oil in it to facilitate initial lubrication.
Switch Adjustments Note: Please contact AXI International before adjusting either the Vacuum or the Pressure Switch to avoid voiding the system’s warranty. Vacuum and Pressure Switches When the value exceeds the set point of the switches’...
Page 15
System Controller. Remove the metal and reset the alarm by pushing or selecting “ALARM RESET” on the System Controller. Note: If any of the above described alarm test procedures fail or if any alarm trip value deviates, immediately contact AXI International.
Maintenance The system should be visually inspected and tested a minimum of every six (6) months according to the procedure below during light duty cycles. Monthly inspections are recommended for systems that are being used in excess of an average of eight (8) hours a day and five (5) days a week. Preventative Maintenance Prior to performing the maintenance procedure ensure that: 1.
Troubleshooting Symptom Troubleshooting Guide No fuel delivery Pump requires too much power 1. Pump does not run 1. Liquid too viscous 2. Pump is not primed 2. Bent Pump Shaft, Binding Rotor 3. Fuel supply line blocked 3. Misalignment of Pump/Motor Coupler 4.
This warranty is not intended to supplant normal inspection, care and service of the products covered by the user, and shall not obligate AXI International to provide free service during the warranty period to correct breakage, maladjustment, or other difficulties arising out of abuse, misuse, or improper care and maintenance of such products. Our...
AXI International reserves the right at any time to make changes in the design, material, function and specifications of its products. Any such changes shall not obligate AXI International to make similar changes in such products that were previously manufactured.
Fort Myers, FL 33905 Tel: +1-239-690-9589 Fax: +1-239-690-1195 Email: info@axi-international.com Internet: www.axi-international.com Please provide the following information: Serial Number of your system, the required part numbers and quantity. The drawings/parts list included in this manual are the most accurate source of part numbers.