Savant Power Storage 20 Installation Manual page 31

Hide thumbs Also See for Power Storage 20:
Table of Contents

Advertisement

The Status Indicator on BCMS module/battery system keeps blinking blue for over 60 seconds.
Battery system failed in self-inspection. Reboot the battery system.
The Status Indicator on at least one battery module keeps blinking blue for over 30 seconds.
Failure in CAN communication. Reconnect communication cable between BCMS and battery module, then reboot the system. Refer to
more information.
The Status Indicator on BCMS module/battery system/battery module is solid yellow while SOC is 0%.
Low battery. Charge the battery.
The Run Indicator on Savant Power Inverter is solid red.
Inverter unit fault, including overload, short circuit, grid over voltage, overfrequency, etc. Check if the load is abnormal. Reboot Savant Power Inverter.
If it does not recover, shut it down and contact us.
Abnormal connection/voltage of batteries. Check battery connection and battery voltage. Reboot Savant Power Inverter. If it does not recover, shut
ESS down and contact Savant support.
The Run Indicator on Savant Power Inverter is solid yellow.
PV charging unit fault, e.g., PV input over-voltage. Check PV input voltage. Reboot Savant Power Inverter. If it does not recover, shut it down and
contact Savant support.
Abnormal connection/voltage of batteries. Check battery connection and voltage. Reboot Savant Power Inverter. If it does not recover, shut it down
and contact Savant support.
The Run Indicator on Savant Power Inverter is blinking green, and the Status Indicator on Savant Power Inverter is blinking blue.
Inverter unit/PV charging unit is updating. Wait until update is finished. If the blinking blue persists, reboot Savant Power Inverter. If it does not recover,
shut it down and contact Savant support.
The Status Indicator on Savant Power Inverter is blinking red.
Communication fault between energy management unit and battery system. Reboot Savant Power Inverter, then reboot battery system. If it is not
recovered, shut it down and contact Savant support.
Communication fault between energy management unit and inverter unit/PV unit. Reboot Savant Power Inverter. If it does not recover, shut it down
and contact Savant support.
The Status Indicator on Savant Power Inverter is solid red.
Energy management unit internal communication fault. Reboot Savant Power Inverter. If it does not recover, shut it down and contact Savant support.
The Status Indicator on Savant Power Inverter is blinking green.
System is turned off by energy management unit, which might be caused by low battery, over temperature, low temperature, or over current of battery.
Reboot battery system. If it does not recover, shut it down and contact Savant support.