3.3. Internal Wiring

1.
Unfasten the screws from the battery storage wiring cover and wiring panel of the
Savant Power Inverter using a 4mm hex screwdriver, removing both cover plates.
2.
Connect the inverter to the battery system with ground wire, Torque: 26.5 lb-in (3
N*m) feeding the ground wire through the BAT/COM to the battery storage wiring
panel.
3.
Connect power, 12V DC and communication cables from the battery system to the
inverter. Insert the wires according to the corresponding colors of the silkscreen on
the terminal.
NOTE: Conductor colors of the 60A unit will differ from the installation guide.