Each Energy PHS3K-M1A User Manual page 56

Table of Contents

Advertisement

Temp is
23
Too High
Temp is
24
Too Low
PV Over
25
Voltage
Grid Volt
26
Over 110%
Grid Volt
27
Out Range
Temperature is
too high
Temperature is
too low
Over voltage in
PV Inputs
The grid is
overloaded by
10% for over 10
minute
Grid voltage is
out of range
54
corresponding grid L, N, E line
correctly
1. Check the ventilation of
installation environment
2. Avoid direct sunlight
Check if the ambient
temperature is below normal
working temperature of
inverters and increase
ambient temperature
1. Check if the input voltage
exceeds the inverter's upper
limit of input voltage.
2. Decrease solar panel
quantity in series
1. Wait for the inverter to
recovery
2. If the impedance of AC
cable is too small, replace it
with a larger size cable
3. Adjust the protection value
limit as permitted by the grid
company
1. If the impedance of AC
cable is too small, replace it
with a larger size cable
2. Adjust the protection value
limit as permitted by the grid
company