Each Energy PHS3K-M1A User Manual page 43

Table of Contents

Advertisement

Australia C
Voltage
Inverter reactive
power
(Q)% of S
New
Voltage
Zealand
Inverter reactive
power
(Q)% of S
Procedures to enable or disable the Volt-var Response Mode:
Step1: go to 'All Set Enable' in the menu of 'TECHNICAL SET' and turn the
status to 'ON'.
Step2: go to 'Special Func' and then go to 'QU Curve'
Step3: enable or disable the 'Volt-var Response Mode' by changing the
status to 'ON' or 'OFF'.
NOTE:
is required to access this part!
6.2.5.9.3 Volt-watt Response Mode
PU CURVE
The PU Curve is enabled by default. The volt-watt response mode varies
the maximum active power output level of the inverter in response to the
voltage at its grid-interactive port. The diagram below is the response
curve required for the volt–watt response according to the standard of
AS/NZS 4777.2:2020.
215 V
44%
supplying
level
rated
207 V
60%
supplying
level
rated
This operation is for maintenance personnel only. Password
ON
230 V
0%
220 V
0%
41
240 V
255 V
0%
60%
absorbing
235 V
244 V
0%
60%
absorbing