Riello 20010541 Installation, Use And Maintenance Instructions page 58

Forced draught gas burner
Table of Contents

Advertisement

Error
Diagnostic code
code
50 ÷ 58
#
60
0
65 ÷ 67
#
70
#
23
26
71
#
0
1
2
3
72
#
73
#
23
26
75
#
1
2
4
16
76
#
85
#
0
1
Bit 7
Valence  128
86
#
0
Bit 0
Valence 1
Bit 3
Valence  8
Bit 4
Valence  16
87
#
0
Bit 0
Valence 1
Bit 3
Valence  8
20010575
Faults - Probable causes - Solutions
Meaning of the REC 27.100A2 system
Internal error
Internal error: no valid load checking device
Internal error
Fuel/air checking error: Calculation position in
modulation
Invalid load
Curve points not defined
Special position not defined
Standby position
Pre-purging position
Post-purging position
Ignition position
Fuel/air internal checking error:
Fuel/air internal checking error: multistep calculation
position
Position calculation, invalid stage load
Position calculation, stage curve points not defined
Fuel/air ratio internal checking error: cyclical data
check
Check synchronisation data, different current load
Check synchronisation data, different target load
Check synchronisation data, different target positions
Check synchronisation data, different positions reached
Fuel/air internal checking error:
Reference error of a servomotor
Reference error of the fuel servomotor
Reference error of the air servomotor
Reference error owing to parameter modification
Fuel servomotor error
Position error
Circuit open
Curve too steep in terms of train ratio
Deviation of section compared with the last reference
Air servomotor error
Position error
Circuit open
Curve too steep in terms of train ratio
56
Recommended measures
Carry out a reset; if the error arises repeatedly, replace the
control box
Carry out a reset; if the error arises repeatedly, replace the
control box
Carry out a reset; if the error arises repeatedly, replace the
control box
No valid load
Adjust the curve points of all the actuators
Set the standby position of all the servomotors used
Set the pre-purging position of all the servomotors used
Set the post-purging position of all the servomotors used
Set the ignition position of all the servomotors used
Carry out a reset; if the error arises repeatedly, replace the
control box
No valid load
Adjust the curve points of all the servomotors
Carry out a reset; if the error arises repeatedly, replace the
control box
The reference of the fuel servomotor was not successful.
It was not possible to reach the reference point.
1. Check if the servomotors have been inverted.
2. Check if the servomotor is blocked or overloaded.
The reference of the air servomotor was not successful.
It was not possible to reach the reference point.
1. Check if the servomotors have been inverted.
2. Check if the servomotor is blocked or overloaded.
The parameterisation of an actuator (e.g. the reference
position) has been modified. This error will be visualised to start
up a new reference.
It was not possible to reach the target position within the
requested tolerance range.
1. Check if the servomotor is blocked or overloaded.
Circuit open shown on the servomotor connection.
1. Check the wiring (the voltage between pin 5 or 6 and 2 of the
X54 connector must be > 0.5 V).
The slope of the curve can correspond to a maximum position
modification of 31° between 2 points of the modulation curve.
Overloading of the servomotor or servomotor subjected to
mechanical torsion.
1. Check if the servomotor is blocked in any point along its
range of action.
2. Check if the torque is sufficient for the application.
It was not possible to reach the target position within the
requested tolerance range.
1. Check if the servomotor is blocked or overloaded.
Circuit open shown on the servomotor connection.
1. Check the wiring (the voltage between pin 5 or 6 and 2 of the
X54 connector must be > 0.5 V).
The slope of the curve can correspond to a maximum position
modification of 31° between 2 points of the modulation curve.
GB