Parameter Modification Procedure - Riello 20010541 Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

The password must only be communicated to the
qualified personnel or the Technical Assistance
Service, and must be kept in a safe place.
WARNING
Once the access procedure has been carried out, the display will
show "PArA" for a few seconds.
P
Select the group of parameters with keys "+" and "-" , and con-
firm by pressing the "i/reset" key.
Within the group you have chosen, scroll through the list with the
keys "+" and "-" . At the end of the list, the display visualises
"End ".
To return to Normal visualisation mode, simultaneously press the
keys "+" and "-" ( ESC ) twice.
6.7

Parameter modification procedure

After accessing the level and group of parameters, the display
visualises the number of the parameter (flashing) on the left, and
the corresponding value on the right.
P
If the value is not visualised, press the key "i/reset" for 1 - 3s.
An example of how to modify the parameter relating to pre-
purging time (no.225) is given below.
Press the key "i/reset" : the value 20 (seconds) will appear.
NOTE:
The unit of measurement of the time is not visualised but is un-
derstood in seconds.
P
/reset
Press the key "+" and increase the value to 25 seconds (flash-
ing). Press the key "i/reset" to confirm and store.
20010575
Start-up, calibration and operation of the burner
V
h min
s
%
ESC
/reset
h
min
s
%
h min s
V
%
6.6.4.2 Allocating the levels of the parameters
The parameters' level is subdivided into groups as shown in Tab.
O.
No.
Parameter
100: ParA
General parameters
Information and identification data of the system.
200: ParA
Checks on the burner
Type of operation, intervention and safety times
of the various phases.
400: Set
Air/fuel modulation curve
Setting of air/fuel adjustment points
500: ParA
Positioning of servomotors
Choice of positions of the air/fuel servomotors in
the various phases.
600: ParA
Servomotors
Setting and addressing of the servomotors.
700: HISt
Log of the errors:
Choice of different visualisation modes for the er-
rors log.
900: dAtA
Process information
Visualisation of information for the remote man-
agement of the burner.
All the parameters are checked in the factory.
Modification/tampering may compromise the
good operation of the burner and cause injury to
people or damage to things. In any case, modifi-
WARNING
cations must be carried out by qualified person-
nel.
To modify a parameter, refer to the "Parameter modification
procedure" .
P
V
To return to the list of parameters, press the keys "+" and "-"
( ESC ) simultaneously.
P
h min
38
GB
h mi
s
%
s
%
Tab. O
/reset
ESC