Riello 20010541 Installation, Use And Maintenance Instructions page 30

Forced draught gas burner
Table of Contents

Advertisement

Column 1
Load loss at combustion head.
Gas pressure measured at the test point 1)(Fig. 26), with:
combustion chamber at 0 mbar;
burner working at maximum output;
Column 2
Pressure loss at gas butterfly valve 2)(Fig. 26) with maximum
opening: 90°.
To know the approximate output at which the burner is operating
at its maximum:
Subtract the combustion chamber pressure from the gas
pressure measured at test point 1)(Fig. 26).
Find, in the Tab. L relating to the burner concerned, column
1, the pressure value closest to the result you want.
Read the corresponding output on the left.
Example with natural gas G 20:
Maximum output operation
Gas pressure at test point 1)(Fig. 26)
Pressure in combustion chamber
13.3 - 2,0
A maximum output of 2000 kW shown in Tab. L corresponds to
11.3 mbar pressure, column 1.
This value serves as a rough guide; the effective output must be
measured at the gas meter.
To know the required gas pressure at test point 1)(Fig. 26), set
the maximum output required from the burner operation, then:
find the nearest output value in the Tab. L for the burner in
question.
Read, on the right (column 1) the socket pressure 1)(Fig. 26).
Add this value to the estimated pressure in the combustion
chamber.
Example with natural gas G 20:
Required burner maximum output operation: 2000 kW
Gas pressure at output of 2000 kW
Pressure in combustion chamber
11.3 + 2,0
pressure required at test point 1)(Fig. 26).
20010575
Installation
=
13.3 mbar
=
2,0 mbar
=
11.3 mbar
=
11.3 mbar
=
2.0 mbar
=
13.3 mbar
28
GB
S8883
1
2
Fig. 26