Table 6.15. Interlock Configurations
Typical Circuit
 Contact factory for availability

Bell Alarm with Lockout

The bell alarm provides remote indication that the circuit
breaker has opened because of an electrical fault. The
Lockout feature is integral to the trip unit. When a Bell
Alarm is supplied with the breaker, the trip unit dial is set
and locked to the manual position. In order to re-close
the breaker, the Lockout button must be pushed in/reset
on the trip unit 1-Form C contact (Tables 6.16 and 6.17).
©2012 General Electric All Rights Reserved
Courtesy of store.ips.us
Interlock Configuration
Type A
1 from 2 way interlock
2 cable configuration
Interlocking between two circuit breakers
One normal power supply
One generator (emergency) supply
Type B
1 from 3 way interlock
6 cable configuration
Interlocking among three circuit breakers
Three power supplies (generator or transformers)
feeding the same busbar but parallel operation is
prevented.
Available on request.
Type C
1 from 3 way interlock
6 cable configuration
Interlocking among three circuit breakers
Two bus sections can be powered by single
transformer (bus coupler closed) or both
transformers (bus coupler open).
Available on request.
Type D
1 from 3 way interlock
6 cable configuration
Interlocking between three circuit breakers
Two normal power supplies not set in parallel.
One power supply may assist the priority circuit.
Available on request.
EntelliGuard® G Circuit Breaker
Section 6 – Accessories Description
Possible Combinations
B1
O
1
O
B1 can close only if B2 is open.
B2 can close only if B1 is open.
B1
O
1
O
O
Only 1 of 3 breakers can be closed.
B1
O
1
O
O
1
O
v
 Any two from three breakers can be closed.
 Any one from three breakers can be closed.
 Two breakers must be closed to prevent the
third breaker from closing.
B1
O
1
O
1
O
 B1 and/or B3 can be closed only if B2 is open.
 B2 can only be closed if B1 and B2 are both
open.
Table 6.16. Bell Alarm Switches
Switch Configuration
One single pole, double throw switch
(1-Form C contact)
Table 6.17. Bell Alarm Ratings (Common NO/NC
Contact Configuration)
Ratings
120 Vac
AC
250 Vac
125 Vac
DC
250 Vac
B2
O
O
1
B2
B3
O
O
O
O
1
O
O
1
B2
B3
O
O
O
O
O
1
1
O
1
O
1
1
O
1
B2
B3
O
O
O
O
O
1
O
1
1
O
Cat. No.
GBAT1R
6 A
6 A
0.5 A
0.25 A
31