Connecting The Cable - Samsung AE RXEDGG Series Installation Manual

Air to water heat pump
Hide thumbs Also See for AE RXEDGG Series:
Table of Contents

Advertisement

Connecting the cable

Power cable specifications
1 phase
Outdoor unit
AE090RXEDEG
The power cable is not supplied with Air to Water Heat pump.
Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code
designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
This Equipment complies with IEC 61000-3-12.
3 Phase
Outdoor unit
AE090RXEDGG
The power cable is not supplied with Air to Water Heat pump.
Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code
designation IEC:60245 IEC 66 / CENELEC:H07RN-F)
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
3.3[MVA] at the interface point between the user's supply and the public system. It is the responsibility of the installer or
user of the equipment to ensure, by consultation with distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to 3.3[MVA].
Rated
Hz
Volts
50
220-240
Rated
Hz
Volts
50
380-415
ENGLISH-20
Voltage Range
Min
Max
Min. Circuit Amps.
198
264
Voltage Range
Min
Max
Min. Circuit Amps.
342
457
MCA
MFA
Max. Fuse Amps.
22 A
27.5 A
MCA
MFA
Max. Fuse Amps.
10 A
16.1 A