Water pipe installation
Connecting strainer
Use a strainer with 50 mesh (Diameter of each hole must be under 0.4 mm, excluding punching plate)
Connect the strainer after checking the direction of the strainer on the water inlet hole as shown in the illustration.
Wind the Teflon tape more than 15 times on the thread of the water pipe before connecting it.
Service port must face downward and angle should be within 45° on the left and the right side.
After installing the strainer, makes sure that there is no water leakage on the connection part.
For normal operation of the product, clean the strainer regularly (more than once a year).
<Front view>

Connecting power and communication cable

Specification of electric wires
Indoor unit
Power supply
1Ø, 220 V/50 Hz
DVM Hydro unit
Max : 242 V
Min : 198 V
1Ø,
220~240 V/50 Hz
Max : 264 V
DVM Hydro
Min : 198V
3Ø,
unit HT
380~415 V/50 Hz
Max : 456.5 V
Min : 342 V
This Equipment complies with IEC 61000-3-12, provided that the short-circuit power Ssc is greater than or equal to 3.881 M
at the interface point between the user's supply and the public system. It is responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network operator if necessary that the equipment is connected
only to a supply with a short-circuit power Ssc greater than or equal to 3.881 M
26
45°
<Side view>
MCCB [A]
ELB [A]
Power cable (mm
X [A],
2.5 mm
X [A]
30 mA,
Installation)
0.1 sec
X [A],
4.0 mm
X [A]
30 mA,
Installation)
0.1 sec
X [A],
2.5 mm
X [A]
30 mA,
Installation)
0.1 sec
Water inlet pipe
Strainer
Earth cable
Communication cable
2
)
(mm
2
)
2
(Single
2
(Single
2
2.5 mm
2
(Single
(mm
2
)
2
0.75~1.5 mm

Advertisement

Table of Contents
loading

Table of Contents