Strip the insulation of the single con-
ductors by 12 mm.
The cable cross section must be
2
between 1.5 mm
and 10 mm
open the terminal's operating lever and
insert the stripped single conductor in-
to the slot provided, all the way up to
the stop. Then close the operating
lever until it engages.
NOTE!
Only one conductor may be connected
to each pin. The conductors can be
connected without ferrules.
L1´
Phase conductor
N´
Neutral conductor
N´
PEN conductor
NOTE!
The PEN conductor must be produced
with ends that are permanently
marked blue, according to the national
provisions, and have a cross section of
10 mm².
Fasten the ground conductor and PEN
conductor to the ground electrode ter-
minal using a screwdriver (TX20) and a
torque of 1.8-2 Nm.
2