Unigas E115X-FGR M Series Manual Of Installation - Use - Maintenance page 38

Lmv 5x microprocessor controlled gas burners
Table of Contents

Advertisement

PART IV: MAINTENANCE
Gas filter maintenance
To clean or remove the filter, proceed as follows:
1 remove the cap unscrewing the fixing screws (A);
2 remove the filtering cartridge (B), clean it using water and soap, blow it
with compressed air(or replace it, if necessary)
3 replace the cartridge in its proper position taking care to place it
inbetween the guides as not to hamper the cap replacement;
4 be sure to replace the "O" ring into its place (C) and replace the cover
fastening by the proper screws (A).
WARNING: Before opening the filter, close the manual cutoff valve downstream the filter and bleed the gas; check
that inside the filter there is no pressurised gas.
Removing the combustion head
Remove the lid C.
Unscrew the screws V holding in position the manifold G and pull out
the complete group as shown in figure.
Note: for the subsequent assembly carry out the above described
operations in the reverse order, checking the correct position of the OR ring.
To remove the combustion head, pull it out. Once removed, check that the air
and gas holes are not obstructed. Clean the combustion head by means of
compressed air or scrape off the scale using a metallic brush
MultiBloc MBE
MultiBloc VD Mounting
1
2
1. Position VD on VB, fig. 2+3.
2. Slide VD forward up to the stop, fig. 4.
3. Screw VD on with 2 M5 screws for each, max. 5 Nm/44 in.-lb., fig. 5/6.
4. VD can be mounted rotated by 180°, fig. 7.
3
position
A
VRT
AR
OR
4
to push
5
38
B
C
V
C
G
6
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

E140x-fgr m seriesE190x-fgr m seriesE115x-fgrE140x-fgrE190x-fgr

Table of Contents