CPL switch
Set On for setting [BI*_CPL] for respective circuits, if binary input circuits should work
depending on delay and inversion settings. Conversely, set Off if the settings are not required.
Delayed pick-up / delayed drop-off
On-delay and Off-delay timers is provided for each binary input circuit, where the user can
adjust the operation timing. Use settings [On Delay Timer] and [Off Delay Timer].
Logic level inversion
For each BI circuit, the user can invert the pickup signal with setting. When the inversion is
required, set Inverse for setting [INVERSE-SW]. Normal is for non-inversion.
- 660 -
6F2T0207 (0.01)