What is the behaviour when one or more
Gs3
1,2
subscribed GOOSE messages isn't received or
syntactically incorrect (missing GOOSE)
[stNum is out-of-order, or missed]
No fail will be detected.
[sqNum is out-of-order, or missed]
GOOSE subscribe quality
information will become
QUESTIONABLE |
INCONSISTENT (=1100 0000
1000 0). After receiving message
with correct sqNum order, the
quality information is set to
GOOD (=0000 0000 0000 0).
You can assign the information to
any data attribute using our
configuration tool.
GOOSE status change is ignored
The behavior can be changed by
modifying PLC logic.
- 1091 -