Figure 2 shows examples of these failures for Cat 6 patch cords. The plot on the left
shows results from a patch cord made with bad cable. The plot on the right shows
results from a cord with a bad plug.
Low-frequency return loss failure
caused by bad cable
Figure 2. Return Loss Failures at Low and High Frequencies (Cat 6 patch cords)

NEXT Failures

NEXT failures are typically caused by the following:
Excessive untwisting of pairs at plug. Most NEXT failures occur at plugs, where the
twist in the wire pairs is interrupted.
Poor quality plug
Poor quality cable
Poorly matched plug and jack (Cat 6/Class E applications)
Cable compression (pinches, kinks, etc.)
Excessive noise source near cabling under test. Use the impulse noise test to check for
noise.
Wrong test limit selected