Exchanger insulation replacement
•
Isolate the power supply and close the Gas isolation valve to the boiler.
•
Remove the cover of the heat exchanger and the burner (see fig. 43 Removing the burner and cleaning the heat
exchanger).
•
Remove the ignition electrode (2 x T15 Torx screws) Take care not to damage the gasket, replace if damaged. "1".
•
Rotate the insulating disc "2" and remove it, (Dispose of the damaged insulation pad safely this cannot be reused)
•
Install the new insulation pad to the heat exchanger ensuring its correctly secured to the tab the reassemble the
boiler.
Fan
2
•
Isolate the power supply and close the Gas isolation valve to the boiler.
•
Remove the electrical connection to the fan.
•
Remove the clamp "1" and undo & remove the screws "2".
•
Remove the fan "3" & replace the gasket if damaged.
•
When installing / replacing a fan a combustion calibration must be carried out (see "100% calibration" on page 23).