7.0 Troubleshooting

7.1 Troubleshooting in general

In the event of operating disturbances, the following basic features
should be checked before carrying out actual troubleshooting:
the substation is connected to electricity,
the strainer on the DH supply pipe is clean,
the supply temperature of the DH is at the normal level
(summer, at least 60 °C - winter, at least 70 °C),
the differential pressure is equal to or higher than the normal
(local) differential pressure in the DH network – if in doubt, ask
the DH plant supervisor,
pressure on the system - check the HE pressure gauge.
VI.CW.Y5.02 / LUK42260
Authorized personnel only
Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.