COMMAND MENU __________________________________________________________

From this menu user can apply immediate commands to the UPS.
SOUND.: ON
<ENT> BYPASS
<ENT>CANCEL SHUT
<ENT>LAMP TEST
<ENT>EXIT
SOUND: ON or OFF
Each pressing to ENTER button will change the alarm buzzer enable(on) or disable(off) status.
<ENT> BYPASS
If the user presses the ENTER button, UPS transfers the load to bypass. During bypass <ENTER>START
message is shown instead, meaning that ENTER button will start the inverter and transfers the load to inverter
again.
<ENT>CANCEL SHUT
If shutdown process is active ,ENTER button cancels the shutdown. The shutdown process is
controlled via RS232 port.
<ENT>LAMP TEST
ENTER button starts panel lamps test function. At the same time during test , buzzer beeps.
<ENT>EXIT
If the user presses ENTER button, exits from command menu..

ALARM CODES

The following table shows the alarm and warning messages of the UPS. If an alarm occurs, inverter stops and
the load is transferred to bypass. If a warning message occurs, inverter continues its operation.
Message
A7 BATTERY LOW
A7 BAT.LOW SHUT.
A8 OUTPUT HIGH
A9 OVLD.SHUTDOWN
A9 OVERLOAD
A10 LINE FAILURE
A11 OVERTEMP.
A12 OVERCURRENT
A13 OUTPUT LOW
A14 BATTERY HIGH
A16 BYP INP.BAD
A17 BAT.CB OPEN
A19 BATT.FAULT
A20 BOOST CHARGE
A22 OUTPUT OFF
A23 SERVICE TIME
A42 BATTERY TEST
A48 STATIC BYP
Use Up and Down buttons to move on submenu
class
Warning
Alarm
Alarm
Alarm
Warning
Warning
Warning
Alarm
Alarm
Alarm
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Warning
22