3.2.5 COMMAND MENU

This menu contains UPS commands be carefull while using commands.
Use up and down buttons to move cursor on submenu at the end of page you move to next page.
<ENTER> button applies the related command.
ENTER <BYPASS>
ENTER <BOOST>
ENTER B.TEST > 405
RELAY TEST:OFF
ENTER : MODEM INIT
ALARM SOUND: ON/OFF

3.2.6 TIME MENU

You can see Time and date information of the RTC in the UPS ,also you can set date and time from this
menu.
Follow the arrows to set date and time

3.2.7 SERVICE MENU

This menu contains some helpfull service information and some commands.
Use up and down buttons to move cursor on submenu at the end of page you move to next page.
HOURMETER:00075
MAXLOAD:015 020 025 %
ENTER<FAULT RESET>
FAN MAINT: 01000
BAT MAINT :01200
GEN.MAINT: 00500
LOGOUT: --
If maintenance counters are disabled CANCEL word is shown.
COMMAND MENU Page 1 (Level 1)
ENTER transfer the load to bypass
ENTER start boost charge mode
ENTER start short battery test
Left and right test dry contact relays
ENTER initialize dialup modem
Press enter to select disable alarm buzzer
SERVİCE MENU Page 1 (Level 1)
Total operating hour of the UPS
From power on recorded maximum power
ENTER fault reset
Remaining hours to FAN maintenance
Remaining hours to battery maintenance
Remaining hours to general maintenance
ENTER Exit from service login status