Page 1
INSTRUCTIONS MANUALE D’INSTALLAZIONE NOTICE D’INSTALLATION INSTALLATIONS- ANLEITUNGEN INSTRUCCIONES DE INSTALACIÓN INSTRUÇÕES DE INSTALAÇÃO SDIAS8DC SDIBS9DC Split air conditioner system Condizionatore d’aria split system Climatiseurs split Zweirohrsystem-Klimaanlage Acondicionador de aire Split System Sistema de ar condicionado de Unidades Separadas 37.4255.213.00 05/2021...
CONTENTS 1 - Installation site selection................4 2 - System wiring diagram ................4 3 - Wires’ length, size and delayed fuse .............4 4 - Additional material required for installation (not supplied) ......5 5 - Operating limits ..................5 6 - Accessories supplied with the unit ............5 7 - Tools required for installation (not supplied) ...........5 8 - Dimensions and weight ................6 9 - Installation procedure ................7...
Page 3
When wiring WARNING ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM. • Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.
1 - INSTALLATION SITE SELECTION AVOID • Direct sunlight. • Select an appropriate position from which every corner • Nearby heat sources that may affect unit performance. of the room can be uniformily cooled. • Areas where leakage of flammable gas may be expected. •...
4 - ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED) Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with ● foamed polyethylene (min. thickness 8mm). For tubing dimensions, tubing length and elevation difference limits, see installation manual of outdoor unit.
9 - INSTALLATION PROCEDURE CEILING INSTALLATION Minimum operation and maintenance area. Drill a hole (see table), for the passage of refrigeration Find the place for the installation. The unit can be pipework, condensate pipework and electrical connected in four different positions: at the right- cable.
Page 8
Predispose the fixing of the bracket. Running power Floor installation. electric cable (with a ground wire) between the two Attach the bracket to the wall with the screws, but units (see the table of wire section). do not tighten the screws all the way, so that you Check if the quantity and the rawl plugs type can move the bracket for final adjustment.
Page 9
Wall installation. Under ceiling installation. Open a pre-punched hole for the pipe passage (back or botton panel) hole. Fix the unit under the ceiling. Predispose the condensate drain pipe with a positive slope to the outside, as marked on the internal side.
Page 10
Remove the electrical box cover to operate on the Predispose the terminals of the wire to connect to the terminal strip and connect them. (See electric terminal strip. wiring to connect). Secure inter-unit wire using the supplied clamp. WARNING Loose wiring may cause the terminal to overheat or result in unit malfunction.
10 - REMOTE CONTROL UNIT INSTALLATION To ensure that the air conditioner operates correctly, DO NOT install the remote control unit in the following places: • In direct sunlight. • Behind a curtain or other places where it is covered. •...
- TEST OF THE SYSTEM AND CONTROL OF THE AIR VOLUME TO THE OUTLET GRILLES Below you can find the head curves (static pressure) available at the unit outlet according to the air flow and the speed selected on the remote control: SDIAS8DC m3/h...
Page 13
SDIBS9DC m3/h If the resistances in the air distribution system are too high, the air flow to the outlet grilles can be excessively reduced. In this case it is possible to increase the air flow corresponding to each selected speed by removing the jumper on JP2 of the board as follows.
15 - OUTDOOR/INDOOR UNIT REFRIGERANT CIRCUIT ADDRESS Indoor units that are part of a multisplit system must be properly configured to be able to communicate with the outdoor unit over different channels (Indoor A, Indoor B, etc...) of the communication bus. Each indoor unit address must correspond to the physical connection of the indoor unit to the outdoor unit refrigerant circuit, i.e.: Refrigerant Circuit A <-->...
Page 15
(2) ADDRESS SETTING THROUGH REMOTE CONTROLLER WITH PARAMETER P08 (UP TO 8 INDOOR UNITS) • Press the button for a few seconds. 1 UNIT A UNIT E • Press the arrow until you visualize 08. • Press the button again for a few seconds: the number 2 UNIT B UNIT F 0 (factory setting) at the bottom starts flashing.
16 - MATCH BETWEEN REMOTE CONTROLLER AND INDOOR UNIT (TRANSMISSION CHANNEL) The remote control can be addressed to use up to 4 different units installed in the same room. You can get unified control by using a single remote control for all units or each remote control can be addressed to its own unit, in order to control separately temperature, timer and all other functions.
17 - PARAMETERS TABLE Par. Parameter name Default Values Factory default reset 0 = No action 1 = Reset all remote control parameters to facto- ry default value 2 = Reset all unit parameters to factory default value Software version Software version of the remote controller Carrier frequency 0 = 33 kHz...