8. Technical data

8.1. Technical specifications

VM-3P75CT
VOLTAGE INPUTS
Voltage connection
Input voltage range L-N
Input voltage range L-L
Frequency
CURRENT INPUTS
Current connection
Rated current
COMMUNICATION
VE.Can communication port
Ethernet communication port
Refresh rate
POWER SUPPLY
Type
Switch or circuit breaker
[1]
External fuse
Consumption
Frequency
ENCLOSURE
Material & colour
Voltage connection
Current transformer connection
Protection category
Weight
Dimensions
ENVIRONMENTAL
Indoor/outdoor usage
Operating temperature
Storage temperature
Relative humidity
Altitude
Mains supply voltage fluctuations
Overvoltage category
Pollution degree
STANDARDS
Safety
[1]
Can be omitted if a circuit breaker with a fuse rating of 500mA is used as the isolating device.
Page 14
Victron VM-3P75CT Energy Meter Manual
REL200300100
Direct
85 to 265VAC
150 to 460VAC
50/60Hz
Via current transformers (included - wire length 640mm (25.2in)
75A
Two RJ45 connectors (VE.Can terminators included)
One RJ45 connector, Modbus UDP
100ms
Self-power supply via L1-N
Required as means of a disconnecting device - not included
Required in the neutral conductor - 500mA, not included
1.45W / 3.1VA
50/60Hz
Polycarbonate, blue (RAL5012)
2
Screw terminals 0.25 - 1.5mm
(24 - 16AWG)
Pluggable screw terminals (included)
IP20
370g (including packaging)
90 x 71 x 59mm (3.5 x 2.8 x 2.3in)
Indoor only
From -25 to +55 °C
From -25 to +70 °C
< 90% non-condensing
2000m (6562ft)
±0.1Vin
Cat. III
2
EN-IEC 61010-1