13 Maintenance and service

RXTJ-A_RXTA-C_RXTM-A_RXTP-A
R32 split series
4P728168-1 – 2023.03
NOTICE
General maintenance/inspection checklist. Next to the maintenance instructions in
this chapter, a general maintenance/inspection checklist is also available on the
Daikin Business Portal (authentication required).
The general maintenance/inspection checklist is complementary to the instructions
in this chapter and can be used as a guideline and reporting template during
maintenance.
NOTICE
Maintenance MUST be done by an authorised installer or service agent.
We recommend performing maintenance at least once a year. However, applicable
legislation might require shorter maintenance intervals.
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
Formula to calculate the quantity in CO
refrigerant × total refrigerant charge [in kg] / 1000
DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10 minutes, and measure the voltage at
the terminals of main circuit capacitors or electrical components before servicing.
The voltage MUST be less than 50 V DC before you can touch electrical components.
For the location of the terminals, see the wiring diagram.
b
a
DC+
DC-
i
h
a X30A – compressor lead wire
b X70A – fan motor lead wire
c X80A – reversing solenoid valve lead wire
d LED
e X90A – thermistor lead wire
f X21A – electronic expansion valve lead wire
g X40A – thermal overload relay lead wire
h DB1 - diode bridge
i Multimeter (DC voltage range)
Following symbols may occur on the indoor unit:
Symbol
Explanation
Measure the voltage at the terminals of main circuit capacitors or
electrical components before servicing.
13
2
c
d
e
f
g
Maintenance and service
|