Installation Site Requirements Of The Outdoor Unit - Daikin RXTJ30A2V1B Installer's Reference Manual

Table of Contents

Advertisement

6.1.1 Installation site requirements of the outdoor unit

RXTJ-A_RXTA-C_RXTM-A_RXTP-A
R32 split series
4P728168-1 – 2023.03
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-
ventilated room without continuously operating ignition sources (e.g. open flames,
an operating gas appliance, or an operating electric heater). The room size shall be as
specified in the General safety precaution.
INFORMATION
Also read the following requirements:
"2 General safety
"7.1.3 Refrigerant piping length and height
Mind the following spacing guidelines:
b
a
>50
b
a
>50
(mm)
a Air outlet
b Air inlet
NOTICE
The height of the wall on the outlet side of the outdoor unit MUST be ≤1200 mm.
NOTICE
Do NOT stack the units on each other.
Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit's air outlet causes short
circuit (suction of discharge air). This may result in:
deterioration of the operational capacity;
frequent frost acceleration in heating operation;
disruption of operation due to decrease of low pressure or increase of high
pressure;
a broken fan (if a strong wind blows continuously on the fan, it may start rotating
very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing the wall and
NOT directly exposed to the wind.
4
precautions" [
 7].
>100
>150
b
>150
a
6
Unit installation
|
difference" [
4
 32].
a
>50
b
>100
a
>100
b
Installer reference guide
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents