18 | 2.0 Installation

2.4.2 Rack Installation

NOTES:
When the S4K2UC is installed in a rack, it must be supported by a shelf, xed rails or slide rails on each side. The
factory-supplied rack mount handles cannot support the weight of the UPS. They are used to move the UPS into
and out of the rack and to attach the UPS to the rack.
Mounting hardware and slide rails are sold separately. Contact your local SolaHD representative for these options.
To install a S4K2UC in a rack:
1. Unpack the two slide rail assemblies and mounting hardware from the rack mounting kit (P/N: SRS1832). Slide rail
assembly includes inner member and front and rear members. They are interchangeable between left-hand or right-
hand. Mounting hardware includes M4 screws and M5 screws.
2. Remove inner member of each slide rail assembly by extending it to its outermost position, depressing the retaining
latch and then pulling inner member from bracket assembly (see Figure 8).
Figure 8: Pulling inner member from each bracket assembly
3. Determine the S4K2UC's mounting position inside the racks vertical rails.
CAUTION
!
Install the S4K2UC as low as possible in the rack to reduce the risk of tipping.
4. Attach the rear member of each slide rail assembly to the rack's rails with two factory-supplied M5 screws (see Figure 9).
Figure 9: Installing rear member of each slide rail assembly
Bracket assembly
Retaining latch
Inner member
Vertical pole
M5 screw (4 pcs)
Rear member
Front member