Installation
6.2.3

Changing an electronic module during operation

An electronic module can be hot swapped.
Effects:
}
Module bus communication between the other modules is not interrupted.
}
The configuration data is retained.
}
The module is detected automatically as soon as the module is re-inserted.
Procedure:
1. Removing an electronic module
2. Inserting an electronic module
A new electronic module can be inserted during operation.
Procedure:
}
Inserting an electronic module
Effects:
}
Module bus communication between the other modules is not interrupted.
}
To detect the new module the following steps can be necessary:
– Creating a new configuration or changing an existing configuration
– Download of the configuration to the head module
– Restart of the head module. After a restart, the system behaves as after a warm reset
Operating Manual PSS u2 EF 8DO 0.5A
1003621-EN-03
using a reset pushbutton (see operating manual of the head module, chapter "Reset
pusbutton", section "Carrying out a warm reset (restart)").