Summary of Contents for Pilz PSS u2 ES 6DI 120V AC
Page 1
PSS u2 ES 6DI 120V AC Control system PSS u2 Remote I/O system PSS u2 Operating Manual-1005014-EN-01...
Page 2
Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
General wiring guidelines ......................7.1.1 Connection mechanism for terminal blocks ................Terminal configuration ......................Operation ..........................Display elements and messages ....................Technical details ........................Order reference ........................10.1 Product ............................. 10.2 Accessories ..........................Operating Manual PSS u2 ES 6DI 120V AC 1005014-EN-01...
This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product. This documentation is valid for the product PSS u2 ES 6DI 120V AC. It is valid until new documentation is published.
Page 5
Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PSS u2 ES 6DI 120V AC 1005014-EN-01...
Details of the terminal blocks that can be used are available under "Intended Use". Module features Application of the product PSS u2 ES 6DI 120V AC: Electronic module with digital inputs for standard applications The product has the following features: 6 type 1/3 digital inputs in accordance with IEC 61131-2...
Use of the module outside the areas described in this manual, Any use of the module that is not in accordance with the technical details. The module PSS u2 ES 6DI 120V AC may be used in conjunction with the following ter- minal block:...
Any type of modification has been made (e.g. exchanging components on the PCB boards, soldering work etc.). 3.3.3 Disposal When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating Manual PSS u2 ES 6DI 120V AC 1005014-EN-01...
A signal is always detected and signalled to the head module's PII if it is present for longer than the sum of the following times: – Minimum signal time t signal_min – ST scan time Operating Manual PSS u2 ES 6DI 120V AC 1005014-EN-01...
Page 10
Requirements for the filtered signals: The 0-signal and the subsequent 1-signal together must be present at the input for longer than twice the configured pulse stretch time t stretch Operating Manual PSS u2 ES 6DI 120V AC | 10 1005014-EN-01...
Page 11
Pulse stretching Pulse stretching Stretched signal Stretched signal Duration of 1-signal 1-signal Duration of pulse stretching stretch Stretched 1-signal in the module TRUE Stretched 0-signal in the module FALSE Operating Manual PSS u2 ES 6DI 120V AC | 11 1005014-EN-01...
Page 12
Fig.: Timing diagram: pulse stretching with variable signal duration Legend Module Filtered signal in the module Pulse stretching Pulse stretching Stretched signal Stretched signal Duration of 1-signal 1-signal Duration of pulse stretching stretch Operating Manual PSS u2 ES 6DI 120V AC | 12 1005014-EN-01...
– Switching off the LEDs to display the module and terminal status Standby mode – All module functions are inactive. – The LEDs for displaying the module and terminal status are switched off. Operating Manual PSS u2 ES 6DI 120V AC | 13 1005014-EN-01...
1: "1" signal at the input Bit 1 Input data I1 Bit 2 Input data I2 Bit 3 Input data I3 Bit 4 Input data I4 Bit 5 Input data I5 Bit 6-7 None Operating Manual PSS u2 ES 6DI 120V AC | 14 1005014-EN-01...
6.1.1 Dimensions The dimensions include the backplane, electronic module and terminal block. 12,5 51,1 111,1 Fig.: Dimensions in mm, including backplane, electronic module and terminal block Operating Manual PSS u2 ES 6DI 120V AC | 15 1005014-EN-01...
8-pin ter- minal block 2. The protective coding must be visible on the terminal side 3. Rotate the protective coding until is embed- ded within the terminal block. Operating Manual PSS u2 ES 6DI 120V AC | 16 1005014-EN-01...
Electronic modules may only be plugged or unplugged if the terminal block has been re- moved first. The mechanics of the electronic modules are designed for 20 plug in/out cycles. Operating Manual PSS u2 ES 6DI 120V AC | 17 1005014-EN-01...
Inserting an electronic module 1. Insert the electronic module into the suspen- sion lug on the back- plane. 2. Swivel the electronic module downwards until you hear it click into place. Operating Manual PSS u2 ES 6DI 120V AC | 18 1005014-EN-01...
Page 19
Installation 3. Insert the terminal block into the suspen- sion lug on the module. 4. Swivel the terminal block upwards until you hear it click into place. Operating Manual PSS u2 ES 6DI 120V AC | 19 1005014-EN-01...
2. Press the unlocking mechanism that is shown by the arrow and pull off the electronic module upwards. Operating Manual PSS u2 ES 6DI 120V AC | 20 1005014-EN-01...
Module bus communication between the other modules is not interrupted. The head module may need to be configured and restarted in order for the new module to be detected. Operating Manual PSS u2 ES 6DI 120V AC | 21 1005014-EN-01...
The minimum cable cross section for field connection terminals on the terminal blocks is 0.15 mm (AWG26). The maximum cable cross section for field connection terminals on the terminal blocks is 1.5 mm with ferrules (AWG14) Use copper wiring. Operating Manual PSS u2 ES 6DI 120V AC | 22 1005014-EN-01...
Module in operation and there is a "0"-signal at the input Configuration error Module was inserted in the wrong slot. Internal errors See module's diagnostic log Temperature error: Too warm (1) See module's diagnostic log. Operating Manual PSS u2 ES 6DI 120V AC | 24 1005014-EN-01...
Page 25
After the "too hot" message has been received, if the temperature drops back below the "too warm" threshold value, the module will switch to an error-free state. Legend LED on LED flashes LED flashes briefly LED off Operating Manual PSS u2 ES 6DI 120V AC | 25 1005014-EN-01...
In accordance with the standard EN 60068-2-6 Frequency 8,4 - 150 Hz 10 m/s² Acceleration Shock stress In accordance with the standard EN 60068-2-27 Acceleration 150 m/s² Duration 11 ms Operating Manual PSS u2 ES 6DI 120V AC | 26 1005014-EN-01...
Page 27
Mechanical data Material Housing Mounting type plug-in Dimensions Height 110,8 mm Width 12,5 mm Depth 72,5 mm Weight 35 g Where standards are undated, the 2015-04 latest editions shall apply. Operating Manual PSS u2 ES 6DI 120V AC | 27 1005014-EN-01...
PSS u2 A CE E (10 pc.) Coding elements for electronics modules, 328 860 10 pieces PSS u2 A CE T (10 pc.) Coding elements for terminal block (protect- 328 861 ive coding), 10 pieces Operating Manual PSS u2 ES 6DI 120V AC | 28 1005014-EN-01...
Page 29
Order reference Backplanes Product type Features Order no. PSS u2 B 1 Backplane, 1 slot 328 811 PSS u2 B 4 Backplane, 4 slots 328 810 Operating Manual PSS u2 ES 6DI 120V AC | 29 1005014-EN-01...
Need help?
Do you have a question about the PSS u2 ES 6DI 120V AC and is the answer not in the manual?
Questions and answers