[ VIII Troubleshooting ]

4. Dipswitch setting (Factory setting)

1. Function setting
(1) SW1
Switch position
1
Active Thermistor (Intake air
thermistor)
2
Filter clogging detection
3
Filter life
4
5
Remote display
6
7
8
9
Auto restart after power failure
10
Power start/stop
Factory setting
(All models)
(2) SW3
Switch position
1
Unit type
2
3
4
5
6
Target temperature setting
7
8
Target temprature setting
9
10
1 Setting a dew point temperature
The table below shows the dip switch settings and their corresponding dew point temperatures.
The dew point temperatue can be adjusted by setting dip switches in the control box on the main indoor unit. (only PEFY-
AF1200CFMR-E)
The factory setting is 12.8°C [55°F].
SW3-6
OFF
OFF
ON
ON
HWE13100
Function
Built-in thermistor on the remote
controller
Available
2500 hr
-
Thermo-ON signal
-
-
-
Enabled
Enabled
Function
Main (Evaporator)
-
-
-
-
-
-
-
SW3-8
Dew point temperature
OFF
10°C [50°F]
ON
12.8°C [55°F] (standard factory setting)
OFF
15.6°C [60°F]
ON
[PEFY-AF1200CFM-E]
Preset temperature by RC.
[PEFY-AF1200CFMR-E]
Converted temperature from the preset temperature
by RC and relative humidity of 45%.
Switch setting
ON
-
-
-
-
Switch setting
ON
-
-
-
-
*1
-
*1
-
-
- 24 -
OFF
Indoor unit
Unavailable
100 hr
-
Fan output
-
-
-
Disabled
Disabled
OFF
Reheat (Condensor)
-
-
-
-
*1
-
*1
-
-
GB