Dipswitch Setting (Factory Setting) - Mitsubishi Electric CITY MULTI PEFY-WP10VMS1-E Technical & Service Manual

Hide thumbs Also See for CITY MULTI PEFY-WP10VMS1-E:
Table of Contents

Advertisement

[ VII Troubleshooting ]

5. Dipswitch setting (Factory setting)

1. Function setting
(1) SW1
Switch position
1
Active Thermistor (Intake air
thermistor)
2
Filter clogging detection
3
Filter life
4
Outdoor air intake
5
Remote display
6
Humidifier operation
7
Fan speed
8
Fan speed at heating Thermo-OFF Preset fan speed
9
Auto restart after power failure
10
Power start/stop
1) Adress board
Factory setting
ON
2
3
1
(2) SW3
Switch position
1
Unit type
2
3
4
5
6
7
8
Heating 4-deg up
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
ON
1
2
3
ON
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
1
2
3
4
5
6
7
8
9 10
HWE1209A
Function
4
5
6
7
8
9 10
Function
-
-
-
-
-
-
4
5
6
7
8
9 10
ON
Built-in thermistor on the remote
controller
Available
2500 hr
Enabled
Thermo-ON signal
During heating mode
Low
Enabled
Enabled
ON
Cooling only
-
-
-
-
-
-
Disabled
- 16 -
Switch setting
OFF
Indoor unit
Unavailable
100 hr
Disabled
Fan output
During heating operation
Very low
Follows the setting of SW1-7
Disabled
Disabled
Switch setting
OFF
Heat pump
-
-
-
-
-
-
Enabled
GB

Advertisement

Table of Contents
loading

Table of Contents