[ VIII Troubleshooting ]

5. Dipswitch setting (Factory setting)

1. Function setting
(1) SW1
Switch position
1
Active Thermistor (Intake air ther-
mistor)
2
Filter clogging detection
3
Filter life
4
Outdoor air intake
5
Remote display
6
Humidifier operation
7
Fan speed
8
Fan speed at heating Thermo-OFF Preset fan speed
9
Auto restart after power failure
10
Power start/stop
1) Adress board
Factory setting
(2) SW3
Switch position
1
Unit type
2
3
4
Heater backup
5
6
7
8
Sensible temprature correction
9
Superheat setting tempurature*1
10
Sub cool setting tempurature*1
*1 Please don't use SW3-9,10 as trouble might be caused by the usage condition.
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
HWE08010
Function
Function
-
-
-
-
-
PEFY-P06NMSU-E
PEFY-P15NMSU-E
Switch setting
ON
Built-in thermistor on the remote
controller
Available
2500 hr
Enabled
Thermo-ON signal
During heating mode
Low
Enabled
Enabled
Switch setting
ON
Cooling only
-
-
Enabled
-
-
-
Disabled
-
-
PEFY-P08NMSU-E
PEFY-P18NMSU-E
- 26 -
OFF
Indoor unit
Unavailable
100 hr
Disabled
Fan output
During heating operation
Very low
Follows the setting of SW1-7
Disabled
Disabled
OFF
Heat pump
-
-
Disabled
-
-
-
Enabled
-
-
PEFY-P12NMSU-E
PEFY-P24NMSU-E
GB