[ IX Disassembly Procedure ]

7. Fan and fan motor

Use caution not to pinch any wires.
Use caution; the motor is heavy.
1. According to the instructions provided in section 3-1, re-
move the control box cover.
2. According to the instructions provided in section 3-2, re-
move the control box.
3. According to the instructions provided in section 4-4, re-
move the humidity sensor.
4. To remove the fan (Fig.13, 14, 15)
(1) Loosen the three screws holding the front bell mouth and
remove the bell mouth.
(2) Loosen the Sirocco fan set screw and remove the fan.
(3) Remove the three front fan case fixing screws.
(4) Remove the two motor holder fixing screws.
(5) Loosen the three screws holding the rear bell mouth and
remove the bell mouth.
(6) Slide the fan forward along the railing
HWE13100
Set screw
Fig.13
Fig.14
Motor holder
Motor
Fig.15
- 32 -
Sirocco fan
Bell mouth
Fan case
Sirocco fan
Bell mouth