5.2 Preparations for installation

Damage to mounted parts and components as a result of high temperatures
The motor components get very hot during operation. High temperatures can damage parts
mounted by customers, such as cables manufactured out of materials that are not heat
resistant.
● Temperature-sensitive parts must not come into contact with or be attached to components
● Only use heat-resistant mounting parts. The connecting cables and cable entries must be
Loss of conformity with European directives
In the delivery state, the machine corresponds to the requirements of the European directives.
Unauthorized changes or modifications to the machine lead to the loss of conformity with
European Directives and the loss of the associated warranty.
5.2
Preparations for installation
5.2.1

Requirements for installation

The following requirements must be satisfied prior to starting installation work:
● Staff have access to the operating and installation instructions.
● The machine is unpacked and ready for mounting at the installation location.
● Measure the insulation resistance of the winding before starting any installation work. If the
5.2.2

Insulation resistance and polarization index

Measuring the insulation resistance and polarization index (PI) provides information on the
condition of the machine. It is therefore important to check the insulation resistance and the
polarization index at the following times:
● Before starting up a machine for the first time
● After an extended period in storage or downtime
● Within the scope of maintenance work
The following information is provided regarding the state of the winding insulation:
● Is the winding head insulation conductively contaminated?
● Has the winding insulation absorbed moisture?
50
mounted on the machine.
suitable for the particular application.
insulation resistance lies below the specified value, take appropriate remedial measures.
These remedial measures may necessitate the machine being removed again and
transported.