Carrier FZ4A Installation Instructions Manual page 3

Table of Contents

Advertisement

CAUTION
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property
damage.
For optimum condensate drainage performance in horizontal
installations, unit should be leveled along its length and width.
For horizontal applications having high return static and humid
return air, the Water Management Kit, KFAHC0125AAA, may
need to be used to assist in water management.
FIELD
SUPPLIED
HANGING
STRAPS
UNIT
LOW VOLT
ENTRY
OPTIONS
POWER
ENTRY OPTIONS
Fig. 2 - Slope Coil Unit in Horizontal Left Application
A
FA CT OR Y SHIPPED
HORIZONTAL LEFT
APPLICATION
B
C
HORIZONTAL
DRAIN PAN
Fig. 3 - A- Coil in Horizontal Left Application
NOTE:
Gasket kit number KFAHD0101SLP is required for
horizontal slope coil conversion to maintain low air leak/low sweat
performance.
1. Remove blower and coil access panel and fitting panel. (See
Fig. 4.)
2. Remove coil mounting screw securing coil assembly to
right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil assembly
with condensate pan down. (See Fig. 4.)
5. Attach coil to casing flange using coil mounting screw pre-
viously removed.
6. Make sure the pan cap in the fitting door is properly seated
on the fitting door to retain the low air leak rating of the
unit.
7. Add gaskets from kit KFAHD per kit instructions.
8. Align holes with tubing connections and condensate pan
connections, and reinstall access panels and fitting panel.
A-COIL
HORIZONTAL LEFT
PRIMARY
SECONDARY
DRAIN
DRAIN
018-048 21" (533 mm)
060-060 24" (610 mm)
FRONT SERVICE
CLEARANCE
(FULL FACE
OF UNIT)
1.75" (44 mm)
FILTER ACCESS
CLEARANCE
PRIMARY
DRAIN
SECONDARY
DRAIN
A07566
COIL
BRACKET
COI L
SUPPORT
RAIL
DRAIN PA N
SUPPORT
BRACKET
COIL
BRACKET
PRIMARY DRAIN
HORIZONTAL LEFT
AIR SEAL
ASSEMBLY
SECONDARY DRAIN
HORIZONTAL LEFT
REFRIGERANT
CONNECTIONS
A00072
Make sure liquid and suction tube grommets are in place to prevent
air leaks and cabinet sweating. Install after brazing.
COIL MOUNTING
SCREW
COIL
SUPPORT
RAIL
SLOPE COIL
SKI
DRAINPAN
REFRIGERANT
CONNECTIONS
Fig. 4 - Conversion for Horizontal Right Applications
Horizontal Right Conversion of Units With A- Coils
1. Remove blower and coil access panels. (See Fig. 5.)
2. Remove metal clip securing fitting panel to condensate pan.
Remove fitting panel.
3. Remove 2 snap- in clips securing A- coil in unit.
4. Slide coil and pan assembly out of unit.
5. Remove horizontal drain pan support bracket from coil sup-
port rail on left side of unit and reinstall on coil support rail
on right side of unit. (See Fig. 6.)
REFRIGERANT
AIR SEAL
CONNECTIONS
ASSEMBLY
COIL
SUPPORT
RAIL
COIL
BRACKET
DRAIN PAN
SUPPORT
BRACKET
COIL
SUPPORT
RAIL
COIL
BRACKET
HORIZONTAL
DRAIN PAN
PRIMARY DRAIN
HORIZONTAL RIGHT
SECONDARY DRAIN
HORIZONTAL RIGHT
Fig. 5 - Conversion for Horizontal Right Applications
Using A- Coil
DRAIN PAN
DRAIN PAN
SUPPORT BRACKET
SUPPORT BRACKET
Fig. 6 - Drain Pan Support Bracket
6. Convert air- seal assembly for horizontal right.
a. Remove air- seal assembly from coil by removing 4
screws. (See Fig. 5.)
3
BLOWER
ASSEMBLY
PRIMARY DRAIN
SECONDARY DRAIN
A03001
A
HORIZONTAL
RIGHT
APPLICATION
B
C
A00071
A07571