Data and Installation Instructions
Manual Call Points (MCPs)
S4-348XX range
The manual call points (MCPs) covered in this leaflet are
suitable for installation in GENT analogue addressable
fire alarm system. The product range covered include:
¨
S4-34800 MCP (Glass)
¨
S4-34842 MCP (Glass) with Protective cover
¨
S4-34805 MCP with resettable Element
¨
S4-34845 MCP with resettable Element
and Protective cover
¨
S4-34890 Resettable Element for MCP (Pack of 10)
¨
S4-34891 Glass for MCP (Pack of 10)
¨
S4-34892 Protective cover for MCP (Pack of 5)
¨
S4-34895 Surface Back Box for MCP (Red Plastic)
(Pack of 10)
Call point assembly
87
C
Glass or Resettable element options
Glass
Top
A
Optional Back box
87
43,5
THIS WAY UP
D
The optional back box has recessed centres 'D', 3 at the
top and 1 at the bottom, a maximum of 2 are usable.
4188-855 issue 3_06/10_S4-348XX range of MCP
www.acornfiresecurity.com
042aq
Removable
21
Terminal block
15
Resettable element
Top
B
36
D
www.acornfiresecurity.com
Technical data
Standard
EN54: Part 11: 2001
Dimensions
height 88 mm x width 88 mm
depth 21 mm or 57 mm when
surface mounted
Full assembly weight
110g - approximate
Storage temperature
-30 to 70ºC
Operating temperature -25 to 70°C
Relative Humidity
up to 95%
(Non condensing)
Temperature 25 - 55°C
Emission
BS EN61000-6-3:2001
Residential, Commercial & Light
Industry Class B limits
Immunity
BS EN50130-4: Part 4 :1996
Ingress Protection
IP43 estimated standard type
IP55 estimated with protective
cover and back box
Colour
Red (similar to RAL3020)
Case
ABS engineering plastic
Indicators
Normal
Green LED for status and find
device application
Red LED and Yellow tab for
Active
active or Fire indication
Testing
The mechanism and operation
of the MCP is tested by using a
test key
Terminals
2.5mm
LPCB Approved
S4-34842, S4-34805, S4-34845
and S4-34800
Operating voltage
35V to 41V
Loop
Maximum number
per loop = 200
Load factor = 4
(load factor 1000 max. per loop)
2-way device
Installation
a)
Check the contents of the package:
Component
Call point assembly
Earth Strap
Test Key
Long Screw
Instruction leaflet
i
b)
The call point assembly may be mounted on a
standard electrical box or on the optional red back
box S4-34895.
by Honeywell
2
maximum
Quantity
1
1
1
2
1
1