Chapter 7 Modbus Communication Protocol
AC
drive
status
information
AC drive fault codes 0x3203
Note: Other function code addresses are shown in the "Communication Address" column of
the function code summary table. When using the write command (06H), if the highest bit of the
function code parameter address field is 0, it will only be written to the AC drive RAM, and will not
be stored in the power down, if the high half-byte of the function code parameter address field is 1,
it will be written to EEPROM, that is, stored in the power down, such as F0 group: 0x00XX (write
RAM) 0x10XX (stored in EEPROM).
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
Bit0: 0 - Stop
1-Fairwave operation
Bit1: 0-Non-accelerated
1-Accelerate
Bit2: 0-Non-deceleration
1-Deceleration
Bit3: 0-Positive
1-Reverse
Bit4: 0-AC drive normal
0x3202
1-Faulty
Bit5: 0-Slave normal
1 - Faulty slave or slave in
emergency stop
BIT6: 0-No warning,
1-Early Warning
BIT7: 0-Power-up not completed
1-Power up completed
Fault Code
74
R
R