Chapter 3 Mechanical and Electrical Installation
cables with an external diameter not greater than 50mm are supported every 0.6m; power cables
with an external diameter greater than 50mm are supported every 1.0m. Single-core cables arranged
in a square triangle should be tied with ties every 1.0m. For vertical installations, they should be
fixed at intervals of 1.0m~1.5m.
● The power and control cables should be installed separately on the two sides of the trench on
brackets with a vertical spacing of more than 300 mm. if this is not possible, the power cables
should be placed on the brackets above the control cables.
2) Grounding cable
● The grounding cable alignment must comply with the relevant local standards.
3) Control cable
● The control cable should not be routed parallel to the power cable. If this cannot be avoided, a
minimum distance of 300 mm must be maintained between the control cable and the mains cable.
The control cable and the power cable should be routed in a 90-degree cross.
Note:
◆ High voltage cable ends: According to the requirements of the cable manufacturer, cable
connectors must be installed at the ends, mainly for power cables, and the cable connectors need to
be made by professionals.
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual