Chapter 3 Mechanical and Electrical Installation
2)
Matching the input voltage to the voltage requirements of the AC drive;
3)
The cable diameter and voltage resistance of the input and output shall meet the requirements;
4)
High voltage switches on the power supply side should have effective lightning protection
measures.
3.3.5 Wiring of the Control Circuit
The ACH200 series high voltage AC drive user I/O interface board provides 8 switch inputs,
8 switch outputs, 4 analogue inputs and 5 analogue outputs (switch and analogue can be extended
according to user requirements), while optional relay outputs are supported.
User IO terminal description:
Classifica
Termi
tion
nal
X1
Multi-function input option 1
X2
Multi-function input option 2
X3
Multi-function input option 3
X4
Multi-function input option 4
Switching
X5
Multi-function input option 5
Input
X6
Multi-function input option 6
X7
Multi-function input option 7
Multi-function input option 8, for high
X8
speed pulse output
Y1
Multifunctional output option 1
Y2
Multifunctional output option 2
Y3
Multifunctional output option 3
Y4
Multifunctional output option 4
Switching
Y5
Multifunctional output option 5
Output
Y6
Multifunctional output option 6
Y7
Multifunctional output option 7
Multifunctional output option 8 for high
Y8
speed pulse output
T01
Relay output terminal 1
T02
Relay output terminal 2
T03
Relay output terminal 3
T04
Relay output terminal 4
Relays
Output
T05
Relay output terminal 5
T06
Relay output terminal 6
T07
Relay output terminal 7
T08
Relay output terminal 8
High
speed
High-speed
pulse
HDI
(common X8 terminal)
Impulse
input
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
Functional description of the
terminal
pulse
input
Technical specification
1.
Optocoupler isolated input
with COM
2.
Input voltage must be 24 V
3.
Overhanging terminals
indicate disconnection
4.
Input impedance: 3.3K
5.
Where X8 can be used as a
high-speed pulse input
terminal
1. Optocoupler isolated input
with COM
2. Where Y8 can be used as a
high-speed pulse output
terminal
3. Default weak pull-up to 24V
4. Weak pull-up impedance 12K
Each
relay
open/normally closed output and
the relays have a current carrying
capacity of 3A
1.
Optocoupler isolated input
with COM
terminal
2.
Input voltage must be 24 V
3.
Overhanging terminals
indicate disconnection