Chapter 10 Daily Maintenance
parameters
Transformer
10.2 Inspection and Replacement of Wearable Parts
Some components in the AC drive will wear out or deteriorate in performance during use. To
ensure stable and reliable operation of the AC drive, the AC drive should be subject to preventive
maintenance and replacement of components when necessary.
1)
Anti-dust filter
The dust filter is a filtering device out of the air inlet of the AC drive, used to filter dust and
other particles, and it is recommended to replace and clean it once a month. Replacement method
is as follows:
1. Push the square hole of the protective mesh cover upward.
2. When the bottom of the protective mesh cover can be titled over the square hole of the
door plate, pull the protective mesh cover outward from the bottom; take out the anti-sheng Mu
inside the protective mesh cover.
3. Replace the new anti-exit plate, and then put the shield assembly into the square hole of
the door plate.:
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manua
Motor
1.Vibration, temperature
rise
2. Noise
Input and
1. Input Voltage
output
2. Output current
1. Transformer winding
cabinet
1. The insulation
temperature
resistance between the
Insulation
charged circuit and the
withstand
ground (shell)
voltage
2. Each charged circuit to
ground (shell) and each
other without electrical
connection between the
insulation strength of the
circuit
1. Smooth operation, normal
temperature
2. No abnormal, uneven noise
1. Input voltage is within the specified
range
2. The output current is below the rated
value
1. The temperature of the transformer
1. At an ambient temperature of 20℃
is lower than the limit value of 80
degrees
and relative humidity of 90%, not less
than 100MΩ
2. The test voltage is 1.25 times of the
highest instantaneous voltage in the
circuit (excluding overvoltage) for a
duration of 1min
140