SAFETY
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Follow these important instructions during installation and maintenance of
the IQ Combiner 3.

Safety and Advisory Symbols

DANGER: This indicates a hazardous situation, which if not avoided, will
+
result in death or serious injury.
WARNING: This indicates a situation where failure to follow instructions
*
may be a safety hazard or cause equipment malfunction. Use extreme
caution and follow instructions carefully.
NOTE: This indicates information particularly important for optimal
system operation. Follow instructions carefully.

Safety Instructions

DANGER: Risk of electric shock. Risk of fire. Do not attempt to repair the
+
IQ Envoy; it contains no user-serviceable parts. Tampering with the IQ
Envoy will void the warranty. If the IQ Envoy fails, contact Enphase Cus-
tomer Support for assistance (enphase.com/en-us/support/contact).
DANGER: Risk of electrocution! Do not install CTs when current flowing
+
in the sensed circuit. Always install CT wires in the terminal blocks before
energizing the sensed circuit.
DANGER: Risk of electric shock. Do not use Enphase equipment in a
+
manner not specified by the manufacturer. Doing so may cause death or
injury to persons, or damage to equipment.
DANGER: Risk of electric shock. Be aware that installation of this
+
equipment includes risk of electric shock. Do not install the IQ Combiner
3 without first removing AC power from the Enphase System. Ensure the
power coming from the microinverters is de-energized before servicing
or installing.
DANGER: Risk of electric shock. Risk of fire. Only qualified personnel
+
should troubleshoot, install, or replace the IQ Combiner 3.
DANGER: Risk of electric shock. Improper servicing of the IQ Combiner
+
3 or its components may result in a risk of shock, fire or explosion. To
reduce these risks, disconnect all wiring before attempting any mainte-
nance or cleaning.
DANGER: Risk of electric shock. Always de-energize the AC branch circuit
+
before servicing. While connectors are rated for disconnect under load, it
is a best practice to de-energize before disconnecting.
DANGER: Risk of electric shock. Risk of fire. Only use electrical system
+
components approved for wet locations.
DANGER: Risk of electric shock. Risk of fire. Ensure that all wiring is
+
correct and that none of the wires are pinched or damaged.
DANGER: Risk of electric shock. Risk of fire. Do not work alone. Someone
+
should be in the range of your voice or close enough to come to your aid
when you work with or near electrical equipment. Remove rings, brace-
lets, necklaces, watches etc. when working with batteries, photovoltaic
modules or other electrical equipment.
DANGER: Risk of electric shock. Risk of fire. Before making any connec-
+
tions verify that the circuit breaker(s) are in the off position. Double check
all wiring before applying power.
DANGER: Risk of electric shock. Risk of fire. Do not wire unused termi-
+
nals or terminal blocks on the IQ Envoy.
WARNING: Risk of electric shock. To maintain the warranty,
+
do not modify the dead-front other than to remove filler plates, as
needed.
WARNING: Before installing or using the IQ Combiner 3, read all instruc-
*
tions and cautionary markings in the technical description and on the
equipment.
WARNING: Use the circuit breakers in the Enphase IQ Combiner 3 only
*
for serving Enphase equipment. No other loads are allowed.
WARNING: This unit is not provided with a GFDI device. This inverter or
*
charge controller must be used with an external GFDI device as required by
the Article 690 of the National Electrical Code for the installation location.
Enphase Customer Support: enphase.com/en-us/support/contact
FCC Statement: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy
and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interfer-
ence will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the
equipment off and on, you are encouraged to try to correct the interference by one or
more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and the receiver.
- Connect the equipment into an outlet on a circuit different from that
to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by the party responsible for compli-
ance may void the user's authority to operate the equipment.
This Class B digital apparatus complies with Industry Canada ICES-003.
WARNING: The IQ Combiner 3 has a pre-installed heat shield attached to
*
the enclosure door. Do not remove the heat shield.
WARNING: This product is intended for operation in an environment
*
having a maximum ambient temperature of 46ºC (115ºF).
WARNING: BONDING BETWEEN CONDUIT CONNECTIONS IS NOT AUTO-
*
MATIC AND MUST BE PROVIDED AS PART OF THE INSTALLATION.
NOTE: Perform all wiring in accordance with all applicable local electrical
codes, with the Canadian Electrical Code, Part I, and with the National
Electrical Code (NEC), ANSI/NFPA 70.
NOTE: Protection against lightning and resulting voltage surge must be in
accordance with local standards.
NOTE: Using unapproved attachments or accessories could result in
damage or injury.
NOTE: Install the IQ Combiner 3 in the field with 75°C or higher copper
conductors sized per local code requirements and voltage drop/rise
considerations.
NOTE: Use Class 1 wiring methods for field wiring connections to terminals
of a Class 2 circuit. Use 14 to 6 AWG wire for branch circuits and 14 to 3
AWG for output circuits. Select the wire gauge used based on the protection
provided by the circuit breaker(s)/fuses. Overcurrent protection must be
installed as part of the system installation.
NOTE: To ensure optimal reliability and to meet warranty requirements,
the Enphase IQ Combiner 3 must be installed according to the instruc-
tions in this manual.