1.4

Environmental policy / WEEE

Do not dispose electric tools together with household waste material.
According to European Directive 2012/19/EU on waste electrical and electronic equipment and its
implementation in accordance with national law, electric tools that have reached the end of their life
must be collected separately and returned to an environmentally compatible recycling facility.
2

Model Identification

Power supply 24..220 VAC/VDC ±10% 50/60 Hz – 3 Watt
1 A.I. + 1 relays 5 A + 1 relays 3 A + 1 relay 2 A + 2 SSR + 2 D.I. + 1 A.O. V/mA +
URDR001A
RS485 + CT
3

Technical Data

3.1

General Features

Displays
Operating temperature
Sealing
Material
Weight
3.2

Hardware Features

AI1: configurable via software.
Input: Thermocouple type K, S, R, J,T,E,N,B.
Automatic compensation of cold junction
from -25..85° C.
Thermoresistances: PT100, PT500, PT1000,
Analogue
inputs
Ni100, PTC 1K, NTC 10K (β 3435K)
Input V/mA: 0-1 V, 0-5 V, 0-10 V, 0-20 o 4-20
mA, 0-60 mV.
Pot. Input: 1...150 KΩ.
CT: 50 mA.
Relay outputs Config. as command and alarm output
SSR outputs
Config. as command and alarm output
Configurable as command
Analogue
and alarm output or as retransmission of
output
process / setpoints.
Extended power-supply 24..220 VAC/VDC
Power-supply
±10% 50/60 Hz
3.3

Software Features

Regulation algorithms
Proportional band
Integral time
Derivative time
Controller functions
7 - URDR001A - User manual
4 digits 0,52'', 5 digits 0,30''
Temperature: 0-45° C -Humidity 35..95 uR%. Max. altitude: 2000m
Open type, IP20 (not UL evaluated)
Box and front panel PC UL94V0
Approx. 210 g
ON-OFF with hysteresis.
P, PI, PID, PD with proportional time
0..9999°C o °F
0,0..999,9 sec (0 excludes)
0,0..999,9 sec (0 excludes)
Manual or automatic Tuning, selectable alarm, protection of command
and alarm setpoints.
Tolerance (25° C)
± 0.2% ±1 digit (on F.s.) for thermocou-
ple, thermoresistance and V/mA.
Cold junction accuracy 0.1° C/°C.
Impedence:
0-10 V: Ri>110 KΩ
0-20 mA: Ri<5 Ω
0-40 mV: Ri>1 MΩ
Contacts:
Q1: 5 A - 250 VAC for resistive load.
Q2: 3 A - 250 VAC for resistive load.
Q3: 2 A - 250 VAC for resistive load.
12/24 V, 25 mA.
Configurable:
0-10 V with 40000 points +/-0.2% (on
F.s.) @25 °C; load >= 1 KΩ
4-20 mA with 40000 points +/-0.2% (on
F.s.) @25 °C; load <= 250Ω
Consumption: 3 Watt