Wachendorff URDR001A User Manual page 33

Table of Contents

Advertisement

87
Lower Limit Output Percentage 1
L.L.P. 1
Selects min. value for command output 1 percentage.
0%...100%, Default: 0%.
88
Upper Limit Output Percentage 1
U.L.p. 1
Selects max. value for command output 1 percentage.
0%...100%, Default: 100%.
89
Max Gap Tune 1
m.G.t. 1
Selects the max. process-setpoint gap beyond which the automatic tune recalculates PID
parameters of process 1.
0-10000 [digit
1 p. 54
90
Minimum Proportional Band 1
mn.p. 1
Selects the min. proportional band 1 value selectable by the automatic tune for the P.I.D.
regulation of process 1.
0-10000 [digit
1 p. 54
91
Maximum Proportional Band 1
ma.p. 1
Selects the max. proportional band 1 value selectable by the automatic tune for the P.I.D.
regulation of process 1.
0-10000 [digit
1 p. 54
92
Minimum Integral Time 1
mn. i . 1
Selects the min. integral time 1 value selectable by the automatic tune for the P.I.D. regulation
of process 1.
0.0...1000.0 seconds. Default: 30.0 s.
93
Overshoot Control Level 1
o.c.L. 1
The overshoot control function prevents this event during device switching on or when the
setpoint is modified.
Setting a too low value the overshoot may not be fully absorbed, while with high values the
process could reach the setpoint more slowly.
Disab.
Lev. 1
Lev. 2
94÷97
Reserved Parameters - Group E
Reserved parameters - Group E
GROUP F -
res.
98÷122
Reserved Parameters - Group F
Reserved parameters - Group F
33 - URDR001A - User manual
] (degrees.tenths for temp. sensors). Default: 2.0
] (degrees.tenths for temp. sensors). Default: 3.0
] (degrees.tenths for temp. sensors). Default: 80.0
Lev. 3
Lev. 4
Lev. 5 (Default)
- Reserved
Lev. 6
Lev. 7
Lev. 8
Lev. 9
Lev. 10