199 A.5.o.t.
Alarm 5 Output Type
Defines the output type if the alarm 5 is analogue.
Output 0...10 V. Default
0.10 v
Output 4...20 mA.
4.20ma
200 a.5.Hy.
Alarm 5 Hysteresis
Alarm 5 hysteresis.
-9999..+9999 [digit
201 A.5.L.L.
Alarm 5 Lower Limit
Lower limit selectable for the alarm 5 setpoint.
-9999..+30000 [digit
202 A.5.u.L.
Alarm 5 Upper Limit
Upper limit selectable for the alarm 5 setpoint.
-9999..+30000 [digit
203 a.5.re.
Alarm 5 Reset
Alarm 5 contact reset type (always automatic if
Automatic reset (Default)
A. rEs.
Manual reset (manual reset by keyboard or by digital input)
M. rEs.
Stored manual reset (keeps the output status also after a power failure)
M.rEs.S.
Automatic reset with timed activation. The alarm remains active for the time set on the
A. rEs.t.
parameter 206
again, the alarm conditions must disappear.
204 A.5.S.e.
Alarm 5 State Error
Alarm 5 output status in case of error.
If the alarm output is digital (SSR):
Digital output OFF. Default
off
Digital ouput ON.
on
If the alarm output is 0-10V:
0 V. Default
0 V
10 V.
10 v
If the alarm output is 0-20 mA or 4-20 mA:
0 mA. Default
0 ma
4 mA.
4 ma
20 mA.
20 ma
21.5 mA.
21.5ma
205 rES.
Reserved
Reserved parmeter
206 a.5.de.
Alarm 5 Delay
Alarm 5 Delay.
-60:00..60:00 mm:ss (hh:mm if
Negative value: delay when exit alarm status.
Positive value: delay when enter alarm status
207 A.5.S.p.
Alarm 5 Setpoint Protection
Allows or not to change the alarm 5 setpoint.
Editable by the user (Default)
FrEE
Protected
Lock
Protected and not visualized
HidE
43 - URDR001A - User manual
] (degrees for temp. sensors). Default 0.5.
1 p. 54
] (degrees for temp. sensors). Default 0.
1 p. 54
] (degrees for temp. sensors). Default 1750.
1 p. 54
, even if the conditions generating it are missing. To be able to act
a.5.de.
=
AL.5.F .
=
AL.5.F .
c. Aux
). Default: 00:00.
c. aux
).

Advertisement

Table of Contents
loading

Table of Contents