Valve Time 1
vA.t. 1
Valve time related to command 1 (declared by the manufacturer of the valve)
1...300 seconds. Default: 60.
48
Automatic / Manual 1
a.ma. 1
Enables the automatic/manual selection for command 1
Disabled (Default)
diSab.
Enabled
Enab.
Enabled with memory
En.Sto.
49
Initial State
ini.S.
Choose the state of the controller when turning it on. This only works on the RS485 version or by
enabling the Start/Stop from digital input or
Start (Default)
Start
Stop
stop
Stored. State of Start/Stop prior to switching off.
Store.
50
State Valve Saturation
S.vA.S.
Select the valve status when the output percentage is 100%
The valve opening relay is activated for a time equal to 5% of the valve time
PERc.
The valve opening relay is always active
FiXEd
51
Initial Value Setpoint 1
i.SP. 1
Determines the initial value (at start) of setpoint 1 of command 1 when
parameter 46
c.S.p .1
-9999..+30000 [digit
52÷53
Reserved Parameters - Group C
Reserved parameters - Group C
GROUP D -
res.
54÷72
Reserved Parameters - Group D
Reserved parameters - Group D
GROUP E -
reG. 1
73
Tune 1
tun. 1
Selects autotuning type for command 1
Disabled. If proportional band and integral time paramters are to selected to zero, the
diSab.
regulation is ON/OFF type.. (Default)
Automatic (Automatic P.I.D. parameters calculation )
Auto
Manual (launch by keyboards or by digital input)
Manu.
Once (P.I.D. parameters calculation only at first start)
OncE
Synchronized (Autotuning managed by serial)
SYncH.
74
Setpoint Deviation Tune 1
s.d.t. 1
Selects deviation from command setpoint 1 as threshold used by autotuning to calculate P.I.D.
parameters
0-10000 [digit
1 p. 54
75
Proportional Band 1
p.b. 1
Proportional band or process 1 P.I.D. regulation (Process inertia).
0 ON / OFF if t.i. equal to 0 (Default)
1...10000 [digit
31 - URDR001A - User manual
(Command Setpoint Protection 1)
] (degreesfor temp. sensors). Default 0.
1 p. 54
- Reserved
- Autotuning and PID 1
] (degrees.tenths for temp. sensors). Default: 30.0.
] (degrees.tenths for temp. sensors).
1 p. 54
SET
button.
is selected on
FR.iN.