9.2 Main components

9.2.1 Hydraulic module
7
5.4
9
5.2
6
5.5
4/6 kW without backup heater
7
8
3
8~16 kW without backup heater
Code
Assembly unit
Automatic air purge valve
1
Backup heater(optional)
2
Expansion vessel
3
4
Refrigerant gas pipe
Temperature sensor
5
Refrigerant liquid pipe
6
7
Flow switch
Pump
8
Plate heat exchanger
9
10
Water outlet pipe
11
Pressure relief valve
12
Water inlet pipe
1
2
3
5.3
11
4
8
12
10
4/6 kW with backup heater(optional)
1
5.3
5.4
4
9
10
6
5.5
8~16 kW with backup heater(optional)
Remaining air in the water circuit will be automatically
removed from the water circuit.
Provides additional heating capacity when the heating
capacity of the heat pump is insufficient due to very low
outdoor temperature. Also protects the external water pipes
from freezing.
Balances water system pressure.
Four temperature sensors determine the water and refrigerant
temperature at various points in the water circuit.
5.1-T2B; 5.2-T2; 5.3-T1(optional); 5.4-TW_out; 5.5-TW_in
Detects water flow rate to protect compressor and water pump
in the event of insufficient water flow.
Circulates water in the water circuit.
Transfer heat from the refrigerant to the water.
Prevents excessive water pressure by opening at 3 bar and
discharging water from the water circuit.