Danfoss KP 15A Installation Manual page 3

Pressure control

Advertisement

Manual tripping
(Electrical contacts/wiring test)
LP side
Trip:
use FINGERS ONLY! (Do NOT use screwdriver)
Manual reset
Convertible reset
Insert a screwdriver into the slot on the lock disc and turn it
to desired reset configuration. Do not turn the screw on the
lock disc as it may damage the convertible reset mechanism.
Adjustment spindle(s) location
© Danfoss A/S (AC-MCI / jmn), 2012-11
HP side
Note:
On controls with LP and/or HP man. reset, push corresponding
LP and/or HP man. reset knob during tripping.
To resume control operation after safety cut-out,
push man. reset knob as indicated.
Note:
LP man. reset is possible only after system pressure
has risen above cut-in value.
HP man. reset is possible only after system pressure
has dropped below cut-out value.
Reset options
LP man.
HP man
Note:
Do not select automatic reset if safety
of the system requires manual reset.
Note:
Selected reset configuration may be protected
against unauthorized actions applying a seal.
DKRCI.PI.C00.C1.22 / 520H6064
Use screw
driver only
LP auto.
LP auto.
HP man
HP auto.
LP man.
HP auto.
3