Installation Guide
Pressure Control
Types KP 15, KP 15A, KP 17W, KP 17B, KP 17WB
Refrigerants
KP 15, 17W, 17B, 17WB:
HCFC and non-flammable HFC
KP15A:
R717, HCFC and non-flammable HFC
Ambient temperatures / Mounting requirements
t
min. KP 15: -40 °C (-40 °F)
1
t
min. KP 17: - 25 °C (-13 °F)
1
t
max.:
65 °C (149 °F)
1
Relative humidity RH: 30 – 98%
Vibrations resistance: 4 g (10 – 1000 Hz)
Connections
© Danfoss A/S (AC-MCI / jmn), 2012-11
KP 15, KP 17
Test pressure (P
Type
Regulation range
LP: -0.2 – 7.5 bar
KP 15
HP: 8 – 32 bar
KP 15
LP: -0.9 – 7 bar
LP man. reset
HP: 8 – 32 bar
LP: -0.2 – 7.5 bar
KP 17
HP: 8 – 32 bar
Mounting
Max. 100 °C
(212 °F)
15% Ag
DKRCC.PI.CD0.A4.02 / 520H6074
KP 15, KP 17
KP 15A
)
test
p
max.
test
35 bar (510 psig)
PS/MWP
p
max.
test
20 bar (285 psig)
PS/MWP
Max. working pressure PS/MWP
17 bar / 245 psig
35 bar / 510 psig
17 bar / 245 psig
35 bar / 510 psig
17 bar / 245 psig
35 bar / 510 psig
Enclosure
A:
B:
8 – 32 UNC (M4)
C:
Enclosure IP44
(EN 60529)
Enclosure IP30
(EN 60529)
max. 3 mm
(
1
/
in.)
8
1
Need help?
Do you have a question about the KP 15 and is the answer not in the manual?
Questions and answers