Rinnai E75CRN Installation & Servicing Instructions Manual page 46

High efficiency condensing gas boiler
Table of Contents

Advertisement

Available languages

Available languages

i
NOTICE
i
NOTICE
i
NOTICE
120 V~
Power supply
N
L
1
2
3
4
!
CAUTION
Connection terminal
46
The Rinnai room thermostat and controls must be connected to their allocated
connections. All other types or makes of room thermostats or controls which
are used must have a Volt free contact.
When using an on/off thermostat or control, it may be necessary to calibrate the
anticipating resistance to prevent too high temperature fluctuations. As a standard
rule this means mercury thermostats. This resistance wire is present in the Control
Tower and must be connected to terminals 23 and 27. The anticipating resistance in
the room thermostat has to be set at 0.11 A.
For more detailed questions regarding the components which are not supplied, the
distributor should be contacted.
When wiring an RS100 it is suggested that a jumper be placed on terminals 22
and 23 so that in the event the control is damaged the boiler will still fire based
on outdoor reset.
A jumper should also be used when commissioning or trouble shooting the
boiler.
Power stealing thermostats cannot be connected to terminals 22 and 23.
120 V~
120 V~
120 V~
N
L
N
L
N
5
6
7
8
9
10
CAUTION
Terminals 4 to 11 are for Rinnai use only and not for use in any installation.
Connection terminal E-Series
Cylinder connection
three-way valve
DHW
sensor
L
CH DHW N
11
12
13
14
15
16
Outside
Bus
Room
sensor
Controller
therm.
On / Off
A
B
17
18
19
20
21
23
22
External
24 V~
safety
100 mA
contact
24
25
26
27
figure 22

Advertisement

Table of Contents
loading

This manual is also suitable for:

E50crnE75crpE110crnE110crp

Table of Contents